An interactive installer and systemd-based thermal watchdog for HPE ProLiant Gen10/Gen11 servers. It uses HPE's official Python Redfish tooling (python-ilorest-library — the same engine behind the ilorest RESTful Interface Tool) to optimize fan speeds and reduce unnecessary noise while maintaining safe thermal operating limits.
This tool is designed for deployments where the host OS lacks a compatible HPE AMS/AMSD package path, but iLO Redfish access is available and the platform supports the Oem.Hpe.FanPercentAdjust property on the thermal endpoint. It uses only supported Redfish APIs — no firmware modifications, no unsupported binary patching, no fan hacks.
The installer configures a local service that monitors the iLO thermal endpoint, evaluates designated hardware sensors, and dynamically updates the FanPercentAdjust value based on real-time temperature data.
- quiet: Applied when all monitored sensors remain below warning thresholds.
- normal: Applied when one or more sensors cross a warning threshold.
- safe: Enforced immediately if any sensor crosses a critical threshold, or if Redfish connectivity fails repeatedly (see Max failures).
The service is engineered to fail-safe. Escalation to maximum cooling occurs instantly, while de-escalation back to quieter modes uses hysteresis to prevent rapid fan speed oscillation (fan flapping). If the service stops for any reason, fans revert to full firmware control by default.
On certain HPE platforms — particularly those running unsupported operating systems or non-standard hardware configurations — system fans may run at unnecessarily aggressive speeds despite healthy thermals. This project offers a host-side mitigation via Redfish, removing any operational dependency on the AMSD daemon.
Security is a first-class concern in this tool:
- Always-verified TLS. The installed service never uses
--insecure. During setup the installer pins the iLO's certificate (or you supply a trusted CA/PEM path), and every Redfish call is verified against it via the official library'scafile. - No cleartext credentials. Service credentials are stored as encrypted systemd credentials (
systemd-creds encrypt, systemd ≥ 250, host/TPM-bound) when available, and delivered to the unit viaLoadCredentialEncrypted=. On older systems they fall back to a root-only0400environment file, with a warning suggesting integration with a secrets manager (e.g. HashiCorp Vault). The generated config file contains no secrets. - Least privilege. The dedicated iLO service account is provisioned with only Login and Configure iLO Settings privileges.
- Hardened unit. The systemd service runs with
ProtectSystem=strict,ProtectHome,PrivateTmp,NoNewPrivileges, a managedStateDirectory, and aWatchdogSechealth check. - Explicit permissions. All files are written with strict, explicit modes (secrets
0400, config0600).
- Official tooling: All iLO I/O runs through HPE's official
python-ilorest-library(moduleredfish) via an embedded control-plane helper. - Interactive setup: Driven by a
whiptail-based terminal UI. - Cross-distro dependency management: Installs prerequisites on Debian/Ubuntu (apt), RHEL/Rocky/Fedora (dnf/yum), and OpenSUSE Leap (zypper). Fails cleanly with a useful list on unknown package managers.
- TLS certificate pinning: Fetches and displays the iLO certificate fingerprint for confirmation, then pins it for all future calls.
- Encrypted credential storage:
systemd-credsencryption with a root-only fallback. - Account automation: Provisions or reuses a least-privilege iLO service account, with automatic cleanup of an orphaned account if setup is aborted.
- Compatibility guard: Probes the iLO generation and
FanPercentAdjustcapability and warns clearly if the platform cannot be driven. - Dynamic inventory: Discovers and parses the live sensor list directly from iLO prior to configuration.
- Granular control: Custom sensor selection with per-sensor warning and critical thresholds, configurable poll interval, fan-bias tuning, and a configurable failure threshold (1–10).
- Persistent, watchdog-protected service: A dedicated systemd unit with
sd_notifykeepalive, local state caching to avoid redundant PATCH requests, re-assert-on-start, and revert-on-exit (default ON). - Diagnostics: A formatted
--statusdashboard and a--dry-runmode. - Lifecycle management: Detects existing installs and offers reconfigure, edit, restart, status, logs, and uninstall (optionally deleting the iLO account).
- Version tracking: An embedded
VERSIONis written to the config and shown in the management menu.
The background daemon monitors the following iLO endpoint:
https://<ILO_HOST>/redfish/v1/Chassis/1/Thermal/
The script extracts and processes:
Temperatures[]for monitored sensor tracking.Fans[]to report current RPM metrics.Oem.Hpe.FanPercentAdjustto modify fan behavior.
All requests are made by the embedded Python helper (redfish_ctl.py), which logs into iLO with a verified TLS session and returns a clean JSON envelope to the Bash monitor.
| State | Target Behavior | Default FanPercentAdjust Value |
|---|---|---|
| quiet | Maximum noise reduction when thermals are optimal. | 50 |
| normal | Moderate cooling enhancement upon crossing warning limits. | 25 |
| safe | Standard firmware control; zero offset bias during critical events or failures. | 0 |
Note: Per HPE iLO logic, higher offset values translate to a quieter fan profile within this service's architecture.
The installer pre-selects the following reference sensors when detected on the host:
| Sensor | Warning Threshold | Critical Threshold |
|---|---|---|
| 01-Inlet Ambient | 35°C | 40°C |
| 02-CPU 1 PkgTmp | 75°C | 85°C |
| 05-Chipset | 75°C | 85°C |
| 17-BMC | 75°C | 85°C |
| 20-PCI 1 Zone | 65°C | 75°C |
| 21-M2 Zone | 60°C | 70°C |
| 22-Sys Exhaust 1 | 55°C | 65°C |
- HPE ProLiant Gen10/Gen11 server with active Redfish network access (iLO 5/6).
- Functional Redfish endpoint at
/redfish/v1/Chassis/1/Thermal/exposingOem.Hpe.FanPercentAdjust. - Root privileges on the target host OS.
- One of: Debian/Ubuntu, RHEL/Rocky, Fedora, or OpenSUSE Leap.
The installer automatically installs its prerequisites: whiptail/newt, curl, jq, openssl, python3, python3-pip, and HPE's python-ilorest-library.
TLS note: Verification succeeds cleanly when you connect using the name or IP present in the iLO certificate's subject/SAN. If the default iLO certificate does not include the IP you connect by, connect via the certificate's hostname or regenerate the iLO certificate with the correct SAN — the service intentionally does not weaken verification.
Execute the installer script with root privileges:
chmod +x hpe-fan-watch-installer.sh
sudo ./hpe-fan-watch-installer.sh
- Target definition: Specify the iLO hostname or IP address.
- TLS pinning: Fetch and confirm the iLO certificate fingerprint (or supply a trusted CA/PEM path).
- Credentials: Generate a dedicated least-privilege iLO service account or input existing credentials.
- Compatibility check: Probe iLO generation and
FanPercentAdjustavailability. - Sensor selection: Choose specific hardware sensors to track.
- Threshold definition: Set warning and critical temperature targets.
- Polling frequency: Set the monitoring interval.
- Tuning: Adjust baseline values for quiet, normal, and safe modes.
- Failure threshold: Set how many consecutive Redfish failures force SAFE (1–10).
- Policy: Configure re-assert-on-start, revert-on-exit (default ON), and journal logging.
If the installer detects existing components, it routes to an interactive management menu:
| Menu Option | Action Performed |
|---|---|
| Reconfigure | Falls through to the full setup wizard. |
| Edit config | Opens the config in $VISUAL → $EDITOR → nano/vim/vi; offers to restart afterward. |
| Restart service | Runs systemctl restart and reports status. |
| Show status | Runs hpe-fan-watch.sh --status and displays the dashboard in a scrollable box. |
| Tail logs | Drops to journalctl -u … -n 40 -f; Ctrl+C returns to the menu. |
| Uninstall | Comprehensive teardown (see below). |
- Double-confirmation safety prompt.
- Stops and disables the systemd service (failures surfaced via
whiptail). - Optionally deletes the iLO service account via Redfish, after prompting for an iLO administrator login.
- Deletes all installed files: monitor, unit, config, credentials, pinned certificate, and helper.
- Triggers
systemctl daemon-reload. - Offers to purge the state directory (
/var/lib/hpe-fan-watch).
| Path | Purpose | Mode |
|---|---|---|
/usr/local/sbin/hpe-fan-watch.sh |
Core monitor script | 0750 |
/usr/local/lib/hpe-fan-watch/redfish_ctl.py |
Official-library control-plane helper | 0755 |
/etc/systemd/system/hpe-fan-watch.service |
Systemd unit (watchdog-protected) | 0644 |
/etc/hpe-fan-watch/config |
Configuration (no secrets) | 0600 |
/etc/hpe-fan-watch/ilo.crt |
Pinned iLO TLS certificate | 0644 |
/etc/hpe-fan-watch/ilo.cred |
Encrypted credentials (systemd-creds mode) |
0400 |
/etc/hpe-fan-watch/ilo.env |
Root-only credentials (fallback mode) | 0400 |
/var/lib/hpe-fan-watch/ |
State/cache directory | 0750 |
The core script supports manual execution via the following flags:
# Run a single evaluation cycle and exit
/usr/local/sbin/hpe-fan-watch.sh --once
# Run continuously as a daemon (handled by systemd)
/usr/local/sbin/hpe-fan-watch.sh --daemon
# Print the formatted sensor/fan status dashboard
/usr/local/sbin/hpe-fan-watch.sh --status
# Evaluate and log without writing anything to the iLO
/usr/local/sbin/hpe-fan-watch.sh --dry-run --once
- Support status: This software operates independently as a Redfish-based workaround and is not an officially supported HPE AMSD deployment.
- Firmware compliance: Proper execution depends on the firmware accepting
Oem.Hpe.FanPercentAdjust. iLO 4 (Gen8/Gen9) does not expose this control; the installer warns when it cannot be driven. - Validation requirement: Validate system thermals under sustained production workloads before deploying aggressive noise-reduction profiles.
Use at your own risk. Changing fan profiles impacts hardware cooling. Thoroughly test configurations against your environmental profiles and firmware baselines before broad production rollouts.